Guide · Inert gas systems
Tanker inert gas: the 8% and 5% oxygen limits
Updated 2026-10-08 · About 6 min read
In one sentence
The inert gas system must maintain no more than 8% oxygen by volume throughout cargo tanks at positive pressure and supply gas at no more than 5%; about 11% is only a general combustion boundary for the discussed hydrocarbon mixtures, not an operating limit.
Check three controls separately
| Control point | Requirement and purpose | Tag and source |
|---|---|---|
| Gas supply | Inert gas supplied to cargo tanks: oxygen at or below 5% v/v. | Disclosed[S1] |
| Throughout each cargo tank | Oxygen at or below 8% v/v and positive pressure; atmospheric preparation for entry follows a separate procedure. | Disclosed[S1] |
| Positive pressure | Prevent air ingress during normal operations; a low oxygen reading alone does not establish that the pressure barrier is effective. | Disclosed[S1] |
How to interpret about 11%
Operation and failure checks
- 1
- 2
- 3
Prepare separately for entry
An inerted tank is unsuitable for entry. Ventilation, atmosphere testing and an entry permit are separate requirements.[B2]
8,000 DWT is not the only scope check
- SOLAS II-2/4.5.5.1.2 requires a fixed inert gas system, or an administration-accepted equivalent, for tankers of at least 8,000 DWT constructed on or after 1 January 2016 carrying cargoes described in 1.6.1 or 1.6.2. Older ships, chemical tankers and crude oil washing need separate scope checks.[S2]
Questions
Are 5% supply oxygen and 8% tank oxygen the same measurement?
No. The 5% value concerns supplied inert gas; 8% concerns the atmosphere throughout the cargo tank.
Can crew enter a tank below 8% oxygen?
No. Inerting controls combustion. Crew entry requires separate ventilation, atmosphere testing and an entry permit.
Does one installation rule cover every 8,000 DWT tanker?
No. Construction date, cargo and application provisions matter, with additional requirements for operations such as crude oil washing.